Description:
The AcuDC 262 is an advanced, revenue-grade DC power and energy meter with one voltage input (12–1000Vdc) and two independent current inputs, allowing two DC circuits to be metered and billed from a single unit. Certified to IEC 62053-41 Class 0.5, it measures bi-directional energy per channel and in total, includes cable loss compensation, electronic and physical anti-tamper seals, and three data loggers plus a trend logger. With Modbus RTU over RS485 and Modbus TCP/IP over Ethernet, it targets EV charging, data centre PDUs, battery storage and renewable DC systems.
Key Features:
Revenue-grade accuracy: IEC 62053-41:2021 Class 0.5
One voltage input (12–1000Vdc, 0.1%) and two independent current inputs (0.2%)
Bi-directional energy measurement for each current input and the system total
Current via external shunt (A1, 0–100mV), 4–20mA Hall sensor (A2) or ±5V Hall sensor (A3); shunts from 50A to 4000A
Cable loss compensation for true energy measurement and billing
Electronic and physical anti-tampering seals
Three configurable data loggers plus trend logger; 16MB storage, 1-minute records up to 16 months
Modbus RTU (RS485) and Modbus TCP/IP (100Mbps Ethernet)
256 x 64 pixel LCD display
12–48Vdc SELV power supply, <3W burden
Technical Specifications:
Model: AcuDC 262-1000V – one voltage input up to 1000VDC, two independent current inputs, 12-48VDC supply (P2)
Voltage input: 12.00–1000.00Vdc direct, 0.1% accuracy, 0.01V resolution
Current inputs: 2 channels; A1 shunt 0–100mV, A2 Hall sensor 4–20mA, A3 Hall sensor -5 to +5V; 0.2% accuracy
Supported shunt ratings: 50A, 100A, 200A, 300A, 400A, 500A, 600A, 1000A, 2000A, 4000A
Power accuracy: 0.5%; energy accuracy IEC 62053-41 Class 0.5; charge (Ah) accuracy 0.5%
Power supply (P2): 12–48Vdc SELV, burden <3W
Communications: RS485 Modbus RTU 2400–115200bps; 100Mbps Ethernet Modbus TCP/IP
Data logging: 16MB; 3 data loggers + trend logger; 1-minute interval up to 16 months
Display: LCD 256 x 64 pixels
Operating temperature: -25°C to +70°C; storage -40°C to +85°C; humidity 0–75% RH; altitude 0–2000m
Ingress protection: IP30; recommended installation in IP54 or higher cabinet
Dimensions: 174.0 x 96.0 x 66.5mm (6.85 x 3.78 x 2.82 in)
Standards: IEC 62053-41 Class 0.5, UL 61010-1, UL 61010-2-30, EN55032 Class A, FCC Part 15 Class A, CE
Ordering Options (Current Input Type):
AcuDC 262 1000V-A1-P2 – A1 – two inputs for 0-100mV shunts
AcuDC 262 1000V-A2-P2 – A2 – two inputs for 4-20mA Hall effect sensors
Lead Time:
1 - 3 Days.